When to use Boiler Size Calculator
Estimate boiler output and input from a building heat load and hot-water demand.
Explore a simplified thermal or airflow estimate before a detailed building-services calculation.
How to use this tool
- Enter the inputs listed below. Follow the field format, and select units beside each supported quantity.
- Results update automatically. Review the main result and its breakdown. Use Clear to enter a new scenario.
- Floor area
- Design heating load
- Efficiency (%)
- Domestic hot water load
How it works
Multiply area by the entered design load per square meter. Add any hot-water load, then divide total output by efficiency to find the input capacity.
Worked example
The examples below use fixed sample inputs. They explain the calculation and do not change when you edit the tool above.
- Floor area
- 110 m²
- Design heating load
- 75 W/m²
- Efficiency (%)
- 90
- Domestic hot water load
- 2 kW
- Result
- 11.3888888889 kW
- Required heat output
- 10.25 kW
Understanding the result and its limits
Climate, envelope, occupancy and equipment performance matter. Rules of thumb do not replace a project-specific load or ventilation design.
Frequently asked questions
Can room area alone determine equipment size?
Not reliably. Use the method’s assumptions as an estimate and check the full building conditions before equipment selection.
Methodology and references
Use the formulas and assumptions above when interpreting the example. Any practical estimate depends on the accuracy of the inputs.